Purpose: power supply with intrinsically safe circuits for sensors located in intrinsically hazardous area GOST R 51330.10 (IEC 60079-11-99), GOST 30852.10-2002 (IEC 60079-11-99)Type of explosion protection: intrinsically safe electric circuit of level "ia "Explosion protection marking:[Exia]IExplosive mixtures:according to GOST 30852.11-2002 categories I, IIA, IIB/IIC ExiaIIBPower supply voltage: ~85-250 V, 50 Hz (for each channel)Power consumption: 4 W (for each channel)Output voltage: 24 V (for each channel)Load current: up to 70 mA (for each channel)Galvanic isolation: 3000 V (for each channel)Temperature:Operating temperature range from -40C to +70CShell protection degree: IP20 (GOST 14254-2015)Design: slot designMounting: on DIN-railDimensions (HxWxH): 109x22.5x113 mmWeight: not more than 0.2 kgMaintenance on failure: 100 000 hService life:20 yearsWarranty: 18 months