Purpose: universal module for analogue input (measurement) of voltage or current and discrete output Explosion protection marking:0Ex ia IIC T6 Ga X or PO Ex ia I Ma X Analogue input: 16 single or 8 differential analogue input channels with software-settable ranges of 150 mV, 500 mV, 1 V, 5 V, 10 V, 25 mA Measurement error: not worse than 0.1% Digit capacity:16 digits (ADC )Measuring ranges: independent setting of measuring ranges for each channel ADC sampling frequency: 10 Hz, 28 Hz (default), 200 Hz Single channel sampling time:(set by software) 100 ms, 35 ms (default), 5 ms Sensor monitoring: hardware sensor break diagnosis Galvanic isolation: 2500 V Bandwidth:13.1 Hz Temperature: -40 to +50 C Connection interface: RS-485, Modbus RTU protocol and ADAM-compatible (DCON) Power supply voltage: 10 V to 26 V Power consumption: 0.6 W Dimensions (HxWxG): 109x22.5x113 Warranty: 18 months