Purpose: universal module of analogue input (measurement) of voltage or current and discrete output Explosion protection marking: 0Ex ia IIC T6 Ga X or PO Ex ia I Ma X Analogue input: 8 differential channels of analogue input with software-settable ranges 150 mV, 500 mV, 1 V, 5 V, 10 V, 20 mA Digit capacity: 16 digits Galvanic isolation: 2500 V Bandwidth: 2.62 Hz Measurement error: basic measurement error is not worse than 0.2% Interference coefficient: the coefficient of attenuation of general type interference with a frequency of 50 Hz - not less than 100 dB Temperature: temperature range from -40 to +50 C Connection interface: RS-485, Modbus RTU and DCON protocol Power supply voltage: from 10 V to 13 V Power consumption: 0.6 W OKPD2 Code: 26.51.43.117 Dimensions (HxWxG): 109x22.5x113 Warranty: 18 months