Purpose: module of analogue input of thermocouple signals Explosion protection marking: 0Ex ia IIC T6 Ga X or PO Ex ia I Ma X Analogue input: 8 differential channels for analogue input of thermocouple signals of types J(TZK), K(TCA), B(TPR), L(TCC), E(TCCn), S(TPP 10%), R(TPP 13%), N(TNN), T(TMK), A-1(TWR), A-2(TWR), A-3(TWR) Measurement uncertainty: max: 1 C for ranges J(TCA), K(TCA), T(TMK), E(TCCn); 1.5 C for ranges R(TPP 13%), S(TPP 10%), N(TNN), L(TCC), A-1(TWR), A-2(TWR), A-3(TWR); 2 C for range B(TPR) Digit capacity: 16 digits (ADC) Thermocouple ranges and types: independent setting of thermocouple type for each channel Sensor monitoring: hardware diagnostics of sensor breakage Galvanic isolation: 2500 V Temperature: -40 to +50 C Connection interface: RS-485, Modbus RTU protocol and ADAM-compatible (DCON) Power supply voltage: from 10 V to 26 V Power consumption: 0.72 W Dimensions (HxWxHG): 109x22.5x113 mm Warranty: 18 months