Indicators of short circuit for overhead lines of distribution power grids of high voltage class 110 kV, network frequency 50 Hz, mounted directly on the wires of the controlled line, wire diameter 7-40 mm, with one-way and two-way feeding. IKZ-V42L fixes MFZ from 20 A, has a radio channel of short-range communication of Bluetooth Low Energy (BLE) 2.4 GHz standard, which allows easy setting and adjustment of settings from any smartphone with installed software PPI-3, provides transmission of information about the emergency situation to the control centre via GSM communication (when equipped with BSPI-3L-MR). Indication of alarms by means of LEDs.
Power supply source: Lithium battery (19 Ah). Battery life in standby mode: 7 years. Temperature range: Standard from - 40 deg C to +70 deg C; Extended from - 60 deg C to +85 deg C.
Indicator protection degree IP 68. Faraday cage is used to protect indicators from induced voltage.