Execution
General industrial, Explosion-proof "intrinsically safe circuit i"
Accuracy class
Up to 0.05 C (depending on the type of NCS)
Possibility of simultaneous operation with two TCs using 2-wire scheme or with two TPs using built-in CHS
Armoured glass
Maximum measured temperature
Up to +1820 C
Minimum measured temperature
From minus 210 C
TC connection diagrams
2-, 3-, 4-wire
Compliance with GOST R IEC 61508-2-2012 "Functional safety of electrical, electronic, programmable electronic systems".
Safety Integrity Level 2 (SIL 2)
Mounting of the measuring transducer (MT)
DIN rail
Type of digital protocol
HART v.7 (4...20 mA)
Explosion protection
0Ex ia IIA T6 Ga X, 0Ex ia IIA T5 Ga X, 0Ex ia IIA T4 Ga X, 0Ex ia IIA T3 Ga X, 1Ex ib IIA T6 Gb X, 1Ex ib IIB T6 Gb X, 1Ex ib IIA T5 Gb X, 1Ex ib IIB T5 Gb X, 1Ex ib IIA T4 Gb X, 1Ex ib IIB T4 Gb X, 1Ex ib IIA T3 Gb X, 1Ex ib IIB T3 Gb X, [Ex ia Ga] IIa X
Type (NCC) of primary converter
CWD (ISX), 50M, 100M, 50P, 100P, Pt100, Pt500, Pt1000, 100H, 1000H, TJK(J), TMK (T), TKKn (E), TKK(L), TCA(K), TPP(S), TPP (S), TPP(B), TNN(N), TWR (A-1), -100 mV....+100 mV, -1000 mV...+1000 mV, 400 Ohm, 4000 Ohm, 10 kOhm
Vibration resistance according to GOST R 52931-2008
Group N3
Climatic version
UHL3.1 according to GOST 15150-69 (from minus 60 to plus 70 C)
Degree of protection against dust and moisture
IP20
Power supply voltage
=16...42 B
Overall dimensions
Width 22,5 mm, height 75 mm, depth 80,5 mm
Electromagnetic compatibility (EMC)
IIIA
Inspection interval
Up to 4 years old
Warranty period
24 months (from commissioning) or 36 months (from shipment)
Programmable error current
"Low" (3.7...3.8 mA) or "High" (20...23 mA)