Purpose: discrete input module Explosion protection marking: 0Ex ia IIC T6 Ga X or PO Ex ia I Ma X Discrete input: 16 channels of discrete input with group isolation Overload protection: protection against overvoltage and current overload on input, output, interface, static electricity, etc. Galvanic isolation: 2500 V Logic zero level: max. 2 V Logic one level: 3...12 V Temperature: temperature range from -40 to +50 C Connection interface: RS-485, Modbus RTU and DCON protocol Discrete output: 2 isolated discrete outputs Optional: additionally installed isolated built-in power supply "dry" contacts Supply voltage: from 10 V to 13 V Power consumption: 0.4 W OKPD2 Code: 26.51.43.117 Dimensions (HxWxG): 123x76x33 mm Warranty: 18 months