Ultraviolet flame detector ??329-12M-1 "Nabat UV" has high noise immunity to radiation from the sun and heated objects with a surface temperature up to 1000 ° C
Designed for use at such facilities as compressor and gas pumping stations, chemical industry and fuel and energy facilities, diesel power plants, large sports facilities.
Thanks to the use of a sensor operating in the UV range at wavelengths from 185 to 260 nm, the detector remains operational and does not lose sensitivity in direct sunlight and the presence of heated objects in the field of view.
The detector can be connected to most of the available on the market PPKP with conventional or intrinsically safe loops. It provides both two-wire (detector power supply via an alarm loop) and four-wire (separate power supply line) connections. The current consumed in the standby mode does not exceed 250 µA.
Flame detector "NABAT UV" (IP329-12M-1) in the explosion-proof version is designed for the ...