Purpose: universal module for analogue input (measurement) of voltage or current and discrete output Explosion protection marking: 0Ex ia IIC T6 Ga X or PO Ex ia I Ma X Analogue input: 16 single or 8 differential analogue input channels with software-settable ranges of 150 mV, 500 mV, 1 V, 5 V, 10 V, 20 mA; optional 3 isol channels of digital output, PID and relay controllers Measurement error: not worse than 0.1% Digit capacity: 16 digits (ADC) Measuring ranges: independent setting of measuring ranges for each channel ADC sampling frequency: 10 Hz, 28 Hz (default), 200 Hz Single channel sampling time: (set by software) 100 ms, 35 ms (default), 5 ms Galvanic isolation: 2500 V Bandwidth: 13.1 Hz Temperature: -40 to +50 C Connection interface: RS-485, Modbus RTU and DCON protocol Power supply voltage: from 10 V to 26 V Power consumption: not more than 0.7 W Dimensions (HxWxG): 123x76x33 mm Warranty:18 months