Purpose: module of analogue input of thermocouple signals Explosion protection marking: 0Ex ia IIC T6 Ga X or PO Ex ia I Ma X Analogue input: 8 differential channels of analogue input of thermocouple signals types: J(TCA), K(TCA), B(TPR), L(TCC), E(TCCn), S(TPP 10%), R(TPP 13%), N(TNN), T(TMK), A-1(TWR), A-2(TWR), A-3(TWR) additionally 2 isolated channels of discrete output, PID and relay regulators Measurement error: max: 1C for ranges J(TCA), K(TCA), T(TMK), E(TCCn); 1,5C for ranges R(TPP 13%), S(TPP 10%), N(TNN), L(TCC), A-1(TWR), A-2(TWR), A-3(TWR); 2C for range B (TPR) Digit capacity: 16 digits (ADC) Temperature: -40 to +50 C Connection interface: RS-485, Modbus RTU protocol and ADAM-compatible (DCON) Discrete input: 2 isolated discrete output channels Optional: PID and relay regulators Supply voltage: from 10 V to 26 V Power consumption: not more than 0.72 W Dimensions (HxWxG): 123x76x33 mm Warranty: 18 months