Purpose: measurement of 0...25 mA current onlyConnection: 16 single channels with built-in 49.9 ohm shuntsDischarge capacity: 16 digits (ADC)Galvanic isolation: group isolation of analogue inputs (2500 V)Types of protection: against interface overvoltage, power supply, static electricity, etc.ADC sampling frequency: 10 Hz, 28 Hz (default), 200 Hz Single channel sampling time: (set by software) 100 ms, 35 ms (default), 5 ms Measurement error: basic measurement error not more than 0.1 %Interference coefficient: interference attenuation coefficient of normal/general type interference with frequency 50 Hz - not less than 98/120 dBTemperature: operating temperature range from -40 to +70 SIInterface connection: CAN interfaceProtocols: CANOpenFixing: din-rail mounting ????2 code:26.51.43.117Dimensions (H x W x D): 109x22,5x113 mmWarranty: 18 months