Range of possible distances between receiver and transmitter
8...100 m
Maximum possible width of the space to be protected by one detector
9 m
Maximum possible room area protected by one detector
900
Detector power supply voltage (receiver and transmitter)
10...30 V
Current consumed by the detector in the "Normal" mode (when the transmitter is powered from the receiver via communication line)
0.0025 A
Current consumed by the receiver in "Normal" mode (when the transmitter is powered from a separate source) not more than
0.0025 A
Current consumed by the transmitter when powered from a separate source (in any operating mode) not more than
0.0012 A
Current consumed by the receiver in the mode of forming the output signal "Attention", not more than
0.011 A
Current consumed by the receiver in the mode of forming the output signal "Fire", not more than
0.04 A
Current consumed by the receiver in the mode of forming the output signal "Fault", not more than
0.011 A
Current surge value at formation of the output signal "Attention"
0.00675...0.00825 A
Maximum possible duration of interruptions or polarity reversals of the supply voltage that do not affect normal operation
0.1
Minimum permissible power interruption interval frequency
4
Minimum required duration of power failure to ensure resetting of recorded notifications
2
Typical inertia of detector operation (for "Attention" and "Fire" signals)
5
Maximum inertia of detector actuation (by signals "Attention" and "Fire")
10
Inertia of "Fault" notification fixation in the "Fault - memory" mode
3...5
Inertia of "Fault" notification fixation in the "Fault - tolerance" mode
3...5
Inertia of "Fault" notification fixation in the "Fault - Beam" mode
1.5...2.5
Inertia of "Fault" notification fixation in the "Fault - synchronization" mode
40...70
Inertia of "Fault" notification fixation in the "Fault - failure" mode
40...70
Inertia of "Fault" notification fixation in the "Fault - excess" mode
40...70
Inertia of "Fault" notification fixation in the "Fault - Reduction" mode
40...70
Typical value of resistance of closed contacts of optorelay outputs
15 ohm
Maximum value of resistance of closed contacts of optorelay outputs
25 ohm
Maximum permissible current value switched by the optorelay outputs
0.1 A
Maximum permissible voltage value switched by the optorelay outputs
100 V
Limit value of sensitivity compensation at optical beam power reduction
3
Maximum permissible value of wire resistance of the communication line between the receiver and the transmitter
220 ohm
Weight of receiver and transmitter separately without adjusting device, not more
0.4 kg
Weight of receiver and transmitter separately with alignment device, not more than
0.6 kg
Degree of protection of the shell according to GOST 14254, IP
40