Purpose: intrinsically safe current signal transmission
Intrinsic barrier type: passive
Signal type/sensor: current output signal
Number of sensors to be connected: 1
HART-transparentHART-transparent
Signal parameters or connection method: current loop
Signal range: 0-20 mA
Max. pass resistance of one branch: 300 Ohm
Upper limit of signal range: 24 V / 20 mA
Rated fuse current: 50 mA
Explosion protection marking: [Ex ia] IIC/IIB/I
Protection class of a person against electric shock: 01 according to GOST 12.2.007.0-75
Operating temperature range: -40°C to +70°C
Average MTBF: 100000 hrs.
Average service life, not less than 12 years
Overall dimensions (HxWxH): 99x12,5x114,5
Mounting: on DIN-rail
Degree of protection: IR20 according to GOST 14254-2015
Warranty: 36 months