Basic error
Current and voltage: ± 0.2 %; power: ± 0.5 %; frequency: ± 0.01 Hz; analogue output: ± 0.5 %
Communication interface RS485
Quantity: 1, 2; Protocol: Modbus RTU; Interface exchange rate: 9600, 19200, 38400, 57600 bits/sec.
Overall dimensions, mm
96x96x103(with rear protective cover), 96x96x75,6 (without cover)
LED indication
3 blocks of seven-segment indicators (4 indicators per block); Sign height: 20 mm and 14 mm
Input signal
1 A, 5 A, I/1, I/5 (0 to 2.0-Inom); 100 V, 400 V, U/100 (0 to 1.2-Unom); 45...55 Hz
Measurement time
0.1 sec.
Galvanic isolation of input and output circuits, power supply circuits
Got it
Ethernet Communication Interface
Quantity: 0, 1; 100BASE-TX; Protocols: Modbus TCP, IEC 60870-5-104
Analog outputs
Quantity: 0, 1, 2, 3; Reprogrammable ranges: 0...5 mA, 4...20 mA, 0...20 mA, 0...2.5...5 mA, 4...12...20 mA, 0...10...20 mA, -5...0...+5 mA
Time synchronization
Ethernet (NTP protocol, IEC 60870-5-104); synchronisation accuracy from external source not more than 1 ms; counting accuracy not more than 500 µs; in absence of synchronisation not more than 0,5 sec.
Discrete inputs
Quantity: 0, 4, 6, 8; input signal type "dry contact", voltage at open contacts of the device =24 V, current 10 mA
Discrete outputs
Quantity: 0, 1, 2, 3 (modes: switch on, switch off); =300 V, ~200 V, 100 mA
Power supply voltage
220VU - universal supply: supply voltage from 85 to 270 V AC with frequency 50 Hz or from 100 to 265 V DC; 24VN - (24+12/-6) V DC.
Power consumption from the power supply circuit, not more
15 V?A
Reprogramming
Via the "Configurator" programme (RS485, Ethernet interface) or via the front panel push buttons.
Operating temperature range
-40 to +70 °C (relative humidity 98 % at +35 °C); -40 to +55 °C (relative humidity 95 % at +25 °C) - for devices with "Sea Register" acceptance)
Degree of protection
IP50; IP52 - for devices with "Marine Register" acceptance
Inspection interval
10 years
Warranty period of operation
60 mos.
Average service life, at least
30 years