Purpose: intrinsically safe transmission of current signal from hazardous area to hazardous area and support bidirectional transmission of signals via HART protocol.
Intrinsic barrier type: active with galvanic isolation
Signal type: current 4-20 mA with HART protocol
Connection: 1 channel analogue 4-20 mA current input, 2 channels analogue 4-20 mA current output
Conversion error: not more than ±0.1 per cent
Time of setting of output signal after a sudden change of input signal:not more than 0,2 s
Galvanic isolation: input, channel isolation of outputs, power supply, RS-485 interface - 2500 V
Configuration and data exchange: via RS-485 interface with Modbus RTU protocol.
Power supply voltage: 10-30 V
Power consumption: not more than 5 W
Explosion protection marking:[Ex ia] IIC/IIB/I
Operating temperature range: -40°C to +70°C
Average MTBF: 100 000 h.
Overall dimensions (HxWxH): 99.4x22.5x109
Mounting: on DIN-rail
Degree of protection: IR20
Warranty: 18 months
Tell us what you need and get quotes from verified suppliers