Purpose: intrinsically safe transmission of current signal from hazardous area to hazardous area and support bidirectional transmission of signals via HART protocol.
Intrinsic barrier type: active with galvanic isolation
Signal type/sensor: current 4-20 mA with HART protocol
Connection: 1 analogue input channel of active or passive 4...20 mA signal, 1 analogue output channel of active or passive 4...20 mA signal
Conversion error: basic conversion error of ±0.1 % max.
Galvanic isolation: input, output, power supply - 2500 V
Supply voltage: 10-30 V
Power consumption: not more than 2 W
Explosion protection marking: [Ex ia] IIC/IIB/I
Operating temperature range: -40°C to +70°C
Average MTBF: 120 000 hrs.
Average service life, not less than: 12 years
Overall dimensions (HxWxH): 99x17.6x113.6
Mounting: on DIN-rail
Degree of protection: IR20 according to GOST 14254-2015
Warranty: 18 months
Tell us what you need and get quotes from verified suppliers