Purpose: conversion of signals of thermoelectric converters (thermocouples) and branching into 2 active current signals 4... 20 mA.20 mAConnection: 1 channel of analogue input of thermocouple signals of types J (TZhK), K (TCA), B (TPR), L (TCC), E (TCCn), S (TPP 10%), R (TPP 13%), N (TNN), T (TMK), A-1 (TWR), A-2 (TWR), A-3 (TWR); 2 channels of analogue current output 4... 20 mA; 2 channels of analogue current output 4...20 mDigit capacity: 16 digits (ADC), 12 digits (DAC)Conversion error: not more than 0,1 %, for thermocouples of types B, S, R, A-1, A-2, A-3 not more than 0,15 %Time of output signal establishment after a jump change of input signal: not more than 0,3 sGalvanic isolation: input, channel isolation of outputs, power supply - 2500VTemperature:operating temperature range from -40C to +70CConfiguration: via USB port, NTConfig softwarePower supply voltage: from 10 to 30VPower consumption: not more than 3WDimensions (HxWxH): 109x22,5x113Warranty: 18 months